1 Maria’s Restaurant Lesson 20 Appendix B Zone 2 Manual N Loads
2 Maria’s Restaurant Design(Staff: Maria & 7 Employees each shift. Glass Store Front and front door) C1 R1 F1 Woman’s Restroom 1 handicap 1 standard Men’s Restroom 1 handicap 1 urinal S3 Shelv.. R3 DW Bar 12 X 10 Seating 12 Counter C6 Bar S2 B2 Ice R4 Shelving/Storage 25 ft. Shelv. B1 C7 C2 Fry S1 Restaurant 33 X 15 11 X 4 & 11 X 6 Seating 58 CT/O C3 SP SK H1 R2 F2 WH S1 66 ft. B = Beverage Area R = Refrigerator (blue walk in C = Counter S = Sink; S1 Hand; S2 3 Pot; S3 Bar CT = 4 burner plus flat top over ovens SK= Steam Kettle DW = Dishwasher SP = Salad/cold Prep table F = Freezer (blue walk in) H1 = Hot Prep Table with Heat Lamp Shelf
3 Maria’s Restaurant Design(Staff: Maria & 7 Employees each shift. Glass Store Front and front door) C1 R1 F1 Woman’s Restroom 1 handicap 1 standard Men’s Restroom 1 handicap 1 urinal S3 Shelv.. R3 DW Bar 12 X 10 Seating 12 Counter C6 Bar S2 B2 Ice R4 Shelving/Storage 25 ft. Shelv. B1 C7 C2 Fry S1 Restaurant 33 X 15 11 X 4 & 11 X 6 Seating 58 CT/O C3 SP SK H1 R2 F2 WH S1 66 ft. B = Beverage Area R = Refrigerator (blue walk in C = Counter S = Sink; S1 Hand; S2 3 Pot; S3 Bar CT = 4 burner plus flat top over ovens SK= Steam Kettle DW = Dishwasher SP = Salad/cold Prep table F = Freezer (blue walk in) H1 = Hot Prep Table with Heat Lamp Shelf
4 Total Kitchen Area Equipment Load (Sensible + Latent where applicable)Refrigeration/Freezer: 3, ,778: 7,468 Btuh Dish Washer 4, ,000: 10,600 Btuh Steam Kettle: 2,560 Btuh Two Cook Tops: 16,100 Btuh Convection Ovens: 11,400 Btuh Fryers: 3,800 Btuh Salad Prep Refrigeration: 1,628 Btuh Hot Serve Table: 12,010 Btuh Small Appliances 5,634 +2,120: 7,754 Btuh Kitchen Equipment Total: 73,320 Btuh Total Latent Load: 16,298 Btuh
5 Restaurant & Bar Area EquipmentFor Maria’s Restaurant, the Restaurant and Bar area equipment’s total Btuh value is: 22,186 Btuh The following section shows how the total Btuh was calculated for each piece of equipment shown on the drawing, and then added to some small appliances and restaurant equipment not shown on the drawing Maria has specified electrical circuits for.
6 Zone 2 Speedsheet
7 Speedsheet Location Information
8 Zone 2 Speedsheet TABS
9 Ventilation
10 NOTE: ON ERV EFFICIENCYManual N abridged edition does not allow the use of two different ventilation values for to reflect the efficiency for the ERV. The values when added are: An added 3,268 BTUH Total Cooling Load An added 4,290 BTUH Total Heating Load
11 Infiltration
12 Ducts
13 Internal Loads Lighting & Occupancy
14 Internal Loads EquipmentDiversity Factor: Fraction of active or powered units For internal gains.
15 Floors
16 Ceiling
17 Walls
18 Doors
19 Sky Light & Glass
20 Database
21 N1 Glass
22 N1 Doors
23 N1 Walls, Ceilings & FloorsNet Areas Needed
24 N1 Heating and Cooling Total LoadsTotal Cooling Load = 93, ,631 = 112,266 Btuh Heat Load Sensible Cooling Load Latent Cooling Load
25 Zone 2 Manual N Summary
26 Field Notes For many buildings the ducts are located in an unconditioned space. Thus, the Manual N Speedsheet default setting of T, or the actual duct size can be entered to calculate the heat loss/gain. However, to use the Speedsheet for duct inside of the conditioned space, where the ducts have been previously filled in: to remove the #N/A simply change the T or square foot values to 0.